Duct Size Chart — CFM to Duct Size

A printable duct size chart from 100 to 10,000 CFM. Each row gives the exact required diameter, the next standard round size, a rectangular equivalent and the velocity that results — computed with Darcy-Weisbach and the Altshul-Tsal friction factor, not read off a nomogram.

Advertisement

Chart Basis
Standard air at sea level, 70 °F.
CFM to Duct Size
AirflowRequired ØStandard roundRectangularVelocity
100 CFM6.1 in7 in10" × 5"374 fpm
150 CFM7.1 in8 in12" × 6"430 fpm
200 CFM7.8 in8 in12" × 6"573 fpm
250 CFM8.5 in9 in12" × 6"566 fpm
300 CFM9.1 in10 in14" × 7"550 fpm
400 CFM10.2 in11 in16" × 8"606 fpm
500 CFM11.0 in12 in16" × 8"637 fpm
600 CFM11.8 in12 in16" × 8"764 fpm
800 CFM13.1 in14 in20" × 10"748 fpm
1,000 CFM14.3 in16 in22" × 11"716 fpm
1,250 CFM15.5 in16 in22" × 11"895 fpm
1,500 CFM16.6 in18 in24" × 12"849 fpm
2,000 CFM18.5 in20 in28" × 14"917 fpm
2,500 CFM20.2 in22 in30" × 15"947 fpm
3,000 CFM21.6 in22 in30" × 15"1,136 fpm
4,000 CFM24.1 in26 in36" × 18"1,085 fpm
5,000 CFM26.2 in28 in38" × 19"1,169 fpm
6,000 CFM28.1 in30 in40" × 20"1,222 fpm
8,000 CFM31.3 in32 in44" × 22"1,432 fpm
10,000 CFM34.0 in36 in48" × 24"1,415 fpm

Sizes are the next standard round up from the exact requirement, so the actual velocity shown is slightly lower than the design target.