Duct Fitting Loss Calculator

Elbows, tees, take-offs and dampers often lose more pressure than every foot of straight duct combined. Count the fittings, add the straight run, and get the total the fan has to overcome.

Run Parameters
Airflow and section for this path.
Fittings on this run
Enter a quantity for each fitting present.
FittingCQty
90° elbow, smooth radius, r/D 1.50.15
90° elbow, smooth radius, r/D 1.00.22
90° elbow, 5-piece segmented0.24
90° elbow, 3-piece segmented0.34
45° elbow, smooth radius0.10
90° mitred elbow, no vanes1.20
Tee or cross, flow into the branch1.00
Tee or cross, straight through0.10
45° conical take-off0.50
Gradual reducer, 30° included0.05
Gradual expander, 20° included0.25
Sharp-edged duct entry0.50
Abrupt duct exit1.00
Volume control damper, fully open0.20
Fire damper, curtain type0.50
Flexible connector at the plant0.30
Total Pressure Drop

Enter valid airflow and duct dimensions, then select Calculate.

Calculation basis and data sources
Coefficient source
Representative, rounded loss coefficients based on the ASHRAE Handbook—Fundamentals (2021), Chapter 21 duct-design method. They describe generic fitting geometries rather than edition-specific fitting IDs; use project- or manufacturer-specific data when available.
Fitting-loss method
ΔP = ΣC × Pv. Velocity pressure Pv is calculated from the section velocity and calculated air density; each fitting quantity multiplies its listed coefficient before the values are summed.
Straight-duct method
Darcy–Weisbach friction using the Altshul–Tsal friction-factor approximation and the roughness of the selected duct material. Rectangular sections use the Huebscher equivalent diameter.
Air assumptions
The default is 70 °F dry air at sea-level pressure. Temperature can be changed; altitude remains 0 ft in this calculator. Density and dynamic viscosity are recalculated from the entered temperature.
Units and rounding
Inputs use CFM, inches, feet and °F. Pressure is reported in inches of water gauge; totals are shown to 0.001 in. w.g., friction rate to 0.0001 in. w.g./100 ft, equivalent diameter to 0.1 in. and velocity to the nearest FPM. Calculations retain full precision before display rounding.
Estimate boundary
Results support option comparison and preliminary critical-path estimates. Final design should replace generic coefficients with the actual fitting geometry and verify fan and equipment losses, leakage, balancing, acoustics and adopted-code requirements.