Duct Fitting Loss Calculator
Elbows, tees, take-offs and dampers often lose more pressure than every foot of straight duct combined. Count the fittings, add the straight run, and get the total the fan has to overcome.
Advertisement
Run Parameters
Airflow and section for this path.
Fittings on this run
Enter a quantity for each fitting present.
| Fitting | C | Qty |
|---|---|---|
| 90° elbow, smooth radius, r/D 1.5 | 0.15 | |
| 90° elbow, smooth radius, r/D 1.0 | 0.22 | |
| 90° elbow, 5-piece segmented | 0.24 | |
| 90° elbow, 3-piece segmented | 0.34 | |
| 45° elbow, smooth radius | 0.10 | |
| 90° mitred elbow, no vanes | 1.20 | |
| Tee or cross, flow into the branch | 1.00 | |
| Tee or cross, straight through | 0.10 | |
| 45° conical take-off | 0.50 | |
| Gradual reducer, 30° included | 0.05 | |
| Gradual expander, 20° included | 0.25 | |
| Sharp-edged duct entry | 0.50 | |
| Abrupt duct exit | 1.00 | |
| Volume control damper, fully open | 0.20 | |
| Fire damper, curtain type | 0.50 | |
| Flexible connector at the plant | 0.30 |
Total Pressure Drop
- Total loss on this path
- 0.055 in. w.g.
- Section velocity
- 1,132 FPM
Fittings plus straight duct
- Fitting losses (ΣC × VP)
- 0.000 in. w.g.
- Straight duct loss
- 0.055 in. w.g.
- Sum of loss coefficients ΣC
- 0.00
- Velocity pressure
- 0.080 in. w.g.
- Friction rate
- 0.0923 in. w.g./100 ft
- Equivalent diameter
- 18.0 in