CFM, Velocity & Area Calculator

The continuity equation Q = V × A, solved whichever way you need it — for ducts, grilles, louvers and coil faces.

Inputs

Solve for

Shape

Results

Enter positive values, then select Calculate.

Worked example

A designer needs to know the velocity in a 16 in round branch carrying 1,200 CFM — and whether that fits the acoustic target for an open office.

  1. 1

    Find the free area of a 16 in round duct

    A = π × (16/12)² / 4 = 1.396 ft²

    Diameter in feet, squared, times π/4.

  2. 2

    Solve Q = V × A for velocity

    V = Q / A = 1,200 / 1.396 = 859 FPM

    Same equation the calculator uses, solved for FPM.

  3. 3

    Check against the velocity guidance

    859 FPM is inside typical supply-branch ranges for occupied spaces

    The interpretation card flags when a result drifts toward noise or pressure-drop territory.

Takeaway: One equation, three unknowns — enter any two of CFM, FPM and area and the third falls out. For grilles and louvers, always use the manufacturer's free area, not the face size.

Method and assumptions

  • Q (CFM) = V (FPM) × A (ft²). Area is the free internal cross-section; round A = πD²/4.
  • For grilles, louvers and diffusers use the manufacturer's free (effective) area, not the nominal face size.
  • Rectangular sizes from area are geometric only — for friction-equivalent sizing use the Duct Sizer or Rect ↔ Round converter (Huebscher equivalent diameter).
  • Airflow and velocity shown to the nearest whole unit, area to 0.001 ft².
Was this helpful?
Important Disclaimer

This calculator is for preliminary design guidance only. Final duct sizing, construction, and installation must be performed by qualified professionals and comply with applicable codes and standards.